曹妃甸Design and calculation of industrial coolers

dustrial coolers,design

:本文围绕工业冷却器的设计与计算展开,阐述了工业冷却器在工业生产中的关键作用,其能有效地降低设备或工艺流程的温度,保障系统稳定运行,详细介绍了设计环节,包括依据不同的工业场景和冷却需求确定冷却器的类型,如风冷式、水冷式等,同时考虑冷却介质的特性、流量等参数,在计算方面,着重讲解了热负荷的计算方法,通过分析被冷却对象的热量产生速率、环境温度等因素,精准计算出所需的换热量,还涉及冷却器传热面积、传热系数等关键参数的计算,以确保冷却器能达到预期的冷却效果。

1、Design basis

曹妃甸

曹妃甸Design Standard for Steel Structures GB50017-2017Steel Structure Design Manual, China Construction Industry Press, January 2004

曹妃甸

曹妃甸Code for Construction and Acceptance of Steel Structures (GB50205-2020)

曹妃甸British Code for Design of Steel Structures (BS5950)

曹妃甸

曹妃甸2、Design load

曹妃甸

曹妃甸Load includes structural self weight, wind turbine constant load, live load, snow load, wind load, etc. The structural calculation adopts the ultimate stress method, therefore, the load value is larger than usual. The surface load is calculated based on the distribution coefficient and applied to the platform according to the line load. The wind load is calculated based on the wind vibration coefficient, body shape coefficient, and basic wind pressure to calculate the wind pressure values on four surfaces, which are then converted into line loads and applied to the columns. Auxiliary components such as stair handrails are applied to the stairs according to uniformly distributed loads.

曹妃甸1. Constant load

曹妃甸

曹妃甸The self weight of the steel structure is automatically calculated by the program, and the node weight is considered based on the self weight of the structure multiplied by 1.3. The weight and fluid load of the radiator are applied by external forces.

曹妃甸

Platform constant load: 0.50kN/m2

曹妃甸

2. Live load

Live load of the platform for loading: 2.5kN/m2

曹妃甸

3. Snow load

曹妃甸

According to relevant design data, the snow pressure can be basically calculated as 0.4N/m2.

4. Wind load

曹妃甸

曹妃甸Calculate according to the maximum value.

Basic wind pressure: 0.35kN/m2, height variation coefficient of 1.8, wind vibration coefficient: 1.5, ground roughness category: Class A

曹妃甸

Class.

曹妃甸Is the standard value of wind load, is the wind vibration coefficient at height Z, is the shape coefficient of wind load, and is the coefficient of wind pressure height variation.

曹妃甸

When the standard value of wind load is less than 0.75kpa, calculate based on 0.75 kPa and multiply by 1.4 times the safety factor. Namely

曹妃甸5. Temperature load

The temperature difference is relatively small. The structural form is single, and the linear expansion of steel has a relatively small impact on the overall performance of the structure, which can be ignored.

曹妃甸

曹妃甸6 Earthquake loads

曹妃甸

曹妃甸According to the seismic analysis design method: small earthquakes do not damage, medium earthquakes are repairable, and large earthquakes do not collapse. Small earthquake analysis can be divided into: bottom shear force method, response spectrum analysis, and elastic time history analysis. Medium earthquake analysis is calculated by multiplying small earthquake analysis by amplification factor.

曹妃甸

Seismic fortification intensity: 8 degrees

曹妃甸Design basic seismic acceleration peak value: 0.3g

曹妃甸

曹妃甸Construction site category: II site

曹妃甸Design grouping: Second group

曹妃甸Damping ratio: 0.05

This structure adopts MIADS software for overall modeling and analysis. During modeling, beam elements are mainly used for each structure. In order to facilitate loading, plate elements are established at the structural platform. Consolidation is used as the boundary condition at the bottom of each column, and constraints are applied at the connection between the column and the original structure according to the actual situation. The structure includes upright column, cross brace, slant support and upper and lower platform steel structure.

曹妃甸

曹妃甸Load sub factors and load combinations:

曹妃甸

Number

load

Partial    coefficient remarks

曹妃甸

曹妃甸Partial    coefficient remarks

曹妃甸

1

曹妃甸dead load

曹妃甸

1.3

曹妃甸

曹妃甸2

曹妃甸Dead load, when   it has a restraining effect on uplift and   overturning

曹妃甸1.0

3

曹妃甸Dead load, when   acting together with wind load and live load

1.2

曹妃甸

曹妃甸4

曹妃甸

Live load

曹妃甸1.6

5

曹妃甸

曹妃甸Live load, when   combined with wind load

曹妃甸

1.2

6

曹妃甸Wind load

曹妃甸

1.4

曹妃甸7

曹妃甸

曹妃甸When combined   with wind load and live load

曹妃甸

曹妃甸1.2

3、 Radiator calculation

曹妃甸1. Material parameters

Aluminum alloy adopts 6005-T1, with tensile strength and yield strength equivalent to 6063-T5, tensile strength ≥ 150Mpa, yield stress ≥ 110 Mpa. According to the performance table of aluminum alloy, it is found that 6063-T5 has a tensile strength of 185Mpa, yield stress of 145 Mpa, and fatigue strength of 90MPa.

曹妃甸

2. Working condition analysis

曹妃甸The calculation of radiators can be divided into 1. lifting ondition,

3. operating condition (operating condition is divided into

曹妃甸

曹妃甸4.support and lifting point participate in force simultaneously.

曹妃甸

曹妃甸5.support bears gravity, while lifting point bears horizontal force.

6.support does not bear any force, that is, when the overall structure is subjected to uneven settlement, there is a suspension at the bottom)

曹妃甸

曹妃甸To ensure its stability, it is recommended that the foundation treatment should be pre compressed and settlement assessment should be carried out during the overall installation.

2.1 Hoisting conditions

曹妃甸

At this point, the radiator is only considered for its own weight due to the lack of fluid injection, and is lifted and installed through a side lifting point. Because no other accessories were installed during modeling, in order to estimate the weight more accurately, its self weight coefficient was defined as 1.3.

曹妃甸

The radiator structure consists of 1, frame 2, support beam 3, heat exchange tube 4, tube plate, and other ancillary structures. As the heat exchange tube and support beam are fixed together through a corrugated plate, it can be considered that the heat exchange tube participates in the structural stress, which leads to strain and stress generation.

The overall structural model is

曹妃甸

曹妃甸Radiator structural model

曹妃甸

曹妃甸

曹妃甸

曹妃甸The overall deformation of the radiator during the lifting process

曹妃甸

曹妃甸

曹妃甸Stress cloud diagram of radiator during lifting process

曹妃甸From its displacement cloud map, it can be seen that its overall deformation is 1.2mm, and the maximum stress is 15MPa

曹妃甸

曹妃甸Stress cloud map of heat sink

曹妃甸

曹妃甸

 

曹妃甸

曹妃甸Displacement cloud map of heat sink

曹妃甸

曹妃甸From its displacement cloud map, it can be seen that its overall deformation is 1mm and the maximum stress is 2MPa. Through calculation, it can be seen that horizontal lifting has little effect on the heat dissipation fins, and its deformation and stress are far less than the standard requirements.

曹妃甸

曹妃甸The vertical lifting situation is as follows:

曹妃甸

曹妃甸

曹妃甸Vertical lifting stress cloud map

曹妃甸

曹妃甸

文章版权声明:除非注明,否则均为原创文章,转载或复制请以超链接形式并注明出处。

发表评论

快捷回复: 表情:
AddoilApplauseBadlaughBombCoffeeFabulousFacepalmFecesFrownHeyhaInsidiousKeepFightingNoProbPigHeadShockedSinistersmileSlapSocialSweatTolaughWatermelonWittyWowYeahYellowdog
评论列表 (暂无评论,10339人围观)

还没有评论,来说两句吧...

目录[+]

取消
微信二维码
微信二维码
支付宝二维码